Blowdown Tanks:  Manage Temperature and Pressure

Boiler blowdown tanks are used to reduce the pressure and temperature of the blowdown from a boiler.  IN most states, it is unlawful to discharge blowdown directly into the sewer system.  They typically required boiler blowdown to be reduced to a temperature of 14 F at a maximum pressure of 5PSIG.

The pressurized design allows for heat recovery with the flas steam discharged to the deaerator, or low pressure steam header, and the effluent water passing through a heat exchanger, poisitioned upstream of the deaerator level control valve, to effect make up water tempering.

Blowdown from the boiler is received in the upper part of the blowdown tank.  Because the tank is vented, or connected to a low pressure header, approximately 30% of the blowdown flashes into steam and flows out the vent.  The saturated water that remains falls to the lower half of the tank and forces cold water from the bottom of the tank out the discharge.

Precision Boilers offers blowdown tanks in a variety of sizes.

Blowdown Tanks
Dimensional Data

Components


 

Model Numbers, Ratings, and Dimensions

Model Number*Tank VolumeTank SizeDesign PressDrain (NPT) (in)Shipping Weight (lbs)
(gal)(cu.ft.)Dia (in)HT** (in)
BD-16363041636502320
BD-16484051648502380
BD-16605071660502450
BD20425072042502430
BD206075102060502540
BD-2078100132078502660
BD-2454100132454502590
BD-2468125172468502700
BD-2482150202482502810
BD-3062175233062502800
BD-3070200273070502870
BD-30862503330865021030
BD-36743004036745021090
BD-36863504736865021230
BD-36984005336985021370
BD-42824506042825021550
BD-42905006742905021660
BD-42985507342985021770
BD-48846008048845021800
BD-48987009348985022020
BD-4804750100481045022120
BD-549080010754905022140
BD-5400900120541005022320
BD-54101000133541105022500
BD-6092100013360925022470
BD-60001100147601005022630
BD-60081200160601085022780

*Other sizes and design pressures are available upon request.  **For total height, add 12" for legs and 
6" for vent nozzle.

 Blowdown Tanks

Specification

Note:  items shown in parenthesis () are options.

Blowdown Tank shall be Model __________ as manufactured by Precision Boilers.  The pressure vessel shall be designed for 50 PSI and shall meet the applicable requirements for ASME Section VIII, U-stamped, and National Board Registered.  The manufacturer shall provide the owner with a copy of the Manufacturer's Data Report.  The Tank shall have ______ gallon capacity (total volume), _____ (NPT) (FLG) tangential inlet with wear plate, and properly sized (per National Board recommendations) vent, outlet and outlet restricting orifice.  The tank outer surface shall be painted with one coat of industrial grade red oxide primer.